FLUKE 435 Series II Power Quality and Energy Analyzer

No Price Available

Code Type No. Quantity Price Ex. VAT
K10018 435   No Price Available
Make Enquiry
Delivery Info

Please allow 2 - 5 Business Days for Delivery

Free delivery on all orders over €49.99 + VAT, Click here for more information 

Returns Policy
Click to view complete product details

Fluke 435 Series II Power Quality and Energy Analyzer

 

The Fluke 435-II products are designed for users who need to get to the solution of the power quality problem as quickly as possible so that they can minimize expensive downtime. The measurement process and display of data are optimized to get to the most important information as quickly as possible. Multiple parameters are measured simultaneously and displayed in formats that quickly describe overall power quality health while giving you the detailed information you need to make better maintenance decisions. Data can be quickly accessed as simple digital values, trend graphs that give you fast insight into changes over time, waveforms, phasor diagrams or analyzed and organized into a tabular format such as the event data where the magnitude, duration, and time stamping enable rapid correlation to the problems you are experiencing in your facility.

Features:
  • Quickly see how much money you’re losing due to energy waste in terms of real dollars
  • Easily see how motor startups are affecting motor drive performance
  • Get at a glance power quality health data in real-time so you can make better maintenance decisions
  • Capture every measurement automatically without any set-up so you don’t have to worry about not having the right data
  • Measure all three phases and neutral with the included flexible current probes
  • Highest Safety Rating in the Industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance
Specifications:
Operating Temperature 0 to 40 degree Celsius; 40 to 50 degree Celsius excluding battery
Storage Temperature -20 to 60 degree Celsius
Humidity +10 to 30 degree Celsius: 95 percent RH Non-Condensing
30 to 40 degree Celsius: 75 percent RH Non-Condensing
40 to 50 degree Celsius: 45 percent RH Non-Condensing
Maximum Operating Altitude Up to 2000 metre for CAT IV 600 V, CAT III 1000 V
Up to 3000 metre for CAT III 600 V, CAT II 1000 V
Maximum Storage Altitude 12 km
Volt Model Measurement Range Resolution Accuracy
Vrms (AC + DC) 1 to 1000 volt phase to neutral 0.1 volt ±0.5 percent of nominal voltage
Vpk 1 to 1400 Vpk 1 volt 5 percent of nominal voltage
Voltage Crest Factor 1.0 > 2.8 0.01 ±5 percent
Vrms½ 0.1 volt ±1 percent of nominal voltage
Vfund 0.1 volt ±0.5 percent of nominal voltage
Amps (Accuracy Excluding Clamp Accuracy)
Amps (AC + DC) i430-Flex 1x 5 to 6000 Amps 1 Amps ±0.5 percent ±5 counts
i430-Flex 10x 0.5 to 600 Amps 0.1 Amps ±0.5 percent ±5 counts
1 mV/A 1x 5 to 2000 Amps 1 Amps ±0.5 percent ±5 counts
1 mV/A 10x 0.5 to 200 Amps (AC only) 0.1 Amps ±0.5 percent ±5 counts
Apk i430-Flex 8400 Apk 1 Arms ±5 percent
1 mV/A 5500 Apk 1 Arms ±5 percent
A Crest Factor (CF) 1 to 10 0.01 ±5 percent
Amps½ i430-Flex 1x 5 to 6000 Amps 1 Amps ±1 percent ±10 counts
i430-Flex 10x 0.5 to 600 Amps 0.1 Amps ±1 percent ±10 counts
1 mV/A 1x 5 to 2000 Amps 1 A ±1 percent ±10 counts
1 mV/A 10x 0.5 to 200 Amps (AC only) 0.1 Amps ±1 percent ±10 counts
Afund i430-Flex 1x 5 to 6000 Amps 1 A ±0.5 percent ±5 counts
i430-Flex 10x 0.5 to 600 Amps 0.1 Amps ±0.5 percent ±5 counts
1 mV/A 1x 5 to 2000 Amps 1 Amps ±0.5 percent ±5 counts
1 mV/A 10x 0.5 to 200 Amps (AC only) 0.1 Amps ±0.5 percent ±5 counts
Hz
Fluke 434 at 50 Hz nominal 42.50 to 57.50 Hz 0.01 Hz ±0.01 Hz
Fluke 434 at 60 Hz nominal 51.00 to 69.00 Hz 0.01 Hz ±0.01 Hz
Power
Watts (VA, var) i430-Flex maximum 6000 MW 0.1 watt to 1 MW ±1 percent ±10 counts
1 mV/A maximum 2000 MW 0.1 watt to 1 MW ±1% ±10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ±0.1 percent at nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and volt nominal ±1% ±10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and volt nominal ±1 percent ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts Percent f 0.0 to 100 percent 0.1 percent ±0.1 percent ±n x 0.1 percent
r 0.0 to 100 percent 0.1 percent ±0.1 percent ±n x 0.4 percent
Absolute 0.0 to 1000 volt 0.1 volt ±5 percent
THD 0.0 to 100 percent 0.1 percent ±2.5 percent
Amps Percent f 0.0 to 100 percent 0.1 percent ±0.1 percent ±n x 0.1 percent
r 0.0 to 100 percent 0.1 percent ±0.1 percent ±n x 0.4 percent
Absolute 0.0 to 600 Amps 0.1 Amps ±5 percent ±5 counts
THD 0.0 to 100 percent 0.1 percent ±2.5 percent
Watts Percent f or r 0.0 to 100 percent 0.1 percent ±n x 2 percent
Absolute Depends on clamp scaling and volt nominal ±5 percent ±n x 2 percent ±10 counts
THD 0.0 to 100 percent 0.1 percent ±5 percent
Phase Angle -360 to 0 degree 1 degree ±n x 1 degree
Flicker
Plt, Pst, Pst (1 minute) Pinst 0.00 to 20.00 0.01 ±5 percent
Unbalance
Volts Percent 0.0 to 20.0 percent 0.1 percent ±0.1 percent
Amps Percent 0.0 to 20.0 percent 0.1 percent ±1 percent
Mains Signaling
Threshold Levels Threshold, limits and signaling duration is programmable for two signaling frequencies
Signaling Frequency 60 to 3000 Hz 0.1 Hz  
Relative Voltage Percent 0 to 100 percent 0.10 percent ±0.4 percent
Absolute V3s (3-second average) 0.0 to 1000 volt 0.1 volt ±5 percent of nominal voltage
Includes:
  • Lithium-Ion Battery
  • Power Adapter
  • International Plug Adapter Set
  • Test Lead and Alligator Clip Set
  • Colour Coding Clips and Regional Decals
  • Flexible Current Probes
  • 8 GB SD Card
  • Power Log on CD
  • USB cable A - Mini B
  • Soft Carrying Bag

Transient Detection Each unit is customisable, please contact Our Sales Department for more details on the options available Tel: 091-795000