The installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need. It is compact and lightweight and comes with a padded carrying and waist strap for convenient handling. Operation is intuitive and easily mastered by all levels of workers so you can put it to work immediately for quick and efficient testing to all local regulations. Additional helpful features like On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results. The Fluke two-pole testers are now more rugged and easier to use than ever before. Fast test results the way you need them, with large, easy-to-use buttons, bright backlights, and clear audible and physical indicators designed for any work situation.
1663 Multifunction Tester Features:
- Checks wiring polarity to detect broken N wires
- Measures insulation resistance and loop and line resistance
- Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
- Provides unique zero adapters for fast, reliable and accurate test lead and mains cord compensation
- Measures motor windings with the continuity test
- Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
- Measures RCD switching time and tripping level
- Measures trip time and current for RCD type Amps and AC in one test
- Measures RCD variable current
- Provides automatic RCD test sequence
- Safety rated CAT III 500V, CAT IV 300V
Buy a Fluke 1663 Multifunction Installation tester and get a FREE T6 Electrical Tester and Software
1663 Multifunction Tester Specifications:
AC Voltage Measurement |
Range |
500 volt |
Resolution |
0.1 volt |
Accuracy 45 Hz – 66 Hz |
0.8 percent + 3 |
Input impedance |
360 kΩ |
Overload Protection |
660 volt RMS |
Continuity Testing (RLO) |
Range (Autoranging) |
20/200/2000 Ω |
Resolution |
0.01/0.1/1 Ω |
Open Circuit Voltage |
>4 volt |
Insulation Resistance Measurement (RISO) |
Test Voltage |
50-100-250-500-1000 volt |
Accuracy of Test Voltage (at rated test current) |
+10 percent, -0 percent |
Test Voltage |
50 volt 100 volt 250 volt 500 volt 1000 volt |
Insulation Resistance Range |
20/50 MΩ 20/100 MΩ 20/200 MΩ 20/200/ 500 MΩ 20/ 200/1000 MΩ |
Resolution |
0.01/0.1 MΩ 0.01/0.1 MΩ 0.01/0.1 MΩ 0.01/0.1/1 MΩ 0.01/0.1/1 MΩ |
Test Current |
1 mA at 50 kΩ 1 mA at 100 kΩ 1 mA at 250 kΩ 1 mA at 500 kΩ 1 mA at 1 MΩ |
Loop and Line Impedance (ZI) |
Range |
10/0.001 Ω / High current mΩ mode |
Resolution |
0.01/0.1/1 Ω |
Prospective Earth Fault Current, PSC Test |
Range |
1000 Amps/10 kA (50 kA) |
Resolution |
1 Amps/0.1 kA |
Computation |
Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. |
RCD Testing, RCD Types Tested |
RCD Type |
AC |
Tripping Speed Test (ΔT) |
Current Settings |
10-30-100-300-500-1000 mA – VAR 10-30-100 mA |
Multiplier |
x ½, x 1 x 5 |
Measurement Range |
RCD Type G |
310 ms 50 ms |
RCD Type S |
510 ms 160 ms |
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) |
Current Range |
30 to 110 percent of RCD rated current |
Step Size |
10 percent of IΔN² |
Dwell Time |
Type G |
300 ms/step |
Type S |
500 ms/step |
Measurement Accuracy |
±5 percent |
Specified Trip Current Range (EN 61008-1) |
50 to 100 percent for Type AC 35 to 140 percent for Type A (>10 mA) 35 to 200 percent for Type A (≤10 mA) 50 to 200 percent for Type B 5 percent for Type B |
Earth Resistance Test (RE) |
Range |
200/2000 Ω |
Resolution |
0.1/1Ω |
Frequency |
128 Hz |
Output Voltage |
25 volt |
Phase Sequence Indication |
General Specifications |
Size |
100 x 250 x 125 mm |
Weight |
1.3 Kg |
T150 Voltage and Continuity Tester Specifications:
Battery Type |
AAA Battery |
Voltage AC/DC |
6 to 690 volt |
Continuity |
0 - 400 kΩ |
Frequency |
40 to 400 Hz |
Phase Rotation |
100 to 690 volt |
Resistance Measurement |
Up to 1999 Ω |
Response Time (LED Indicator) |
< 0.5 seconds |
200 kΩ Input Impedance |
Current draw 3.5 mA at 690 volt Current Draw 1,15 mA at 230 volt |
7k Ω Input Impedance (with Load Buttons Pressed) |
Current Draw 30 mA at 230 volt |
Size |
260 x 70 x 38 mm |
Weight |
0.28 kg |
Includes:
- Fluke 1663 Multifunction Tester
- Fluke T150 Voltage and Continuity Testers
- Software CD