Fluke 1663 Multifunction Installation Tester available online - Caulfield Industrial
Go

Fluke 1663 Multifunction Installation Tester

€999.00 Ex Vat

€1228.77 Inc VAT

Fluke 1663 Multifunction Installation Tester View Large Image
P-D11036

See Alternative
Title Quantity Price Availability
Fluke 1663 Multifunction Installation Tester €999.00 Ex Vat €1228.77 Inc VAT
Add To Basket Add to Wishlist

Fluke 1663 Multifunction Installation Tester

 

Fluke 1663 installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need. It is compact and lightweight and comes with a padded carrying and waist strap for convenient handling. Operation is intuitive and easily mastered by all levels of workers so you can put it to work immediately for quick and efficient testing to all local regulations. Additional helpful features like On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

Features:
  • Full-featured tester for installation professionals
  • Tests to all local regulations and provides test results for complete documentation
  • Tests smooth dc sensitive RCDs (Type B)
  • Checks wiring polarity to detect broken N wires
  • Measures insulation resistance and loop and line resistance
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapters for fast, reliable and accurate test lead and mains cord compensation
  • Measures motor windings with the continuity test
  • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)
  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type Amps and AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
Specifications:
Battery Type AA
AC Voltage Measurement
Range 500 volt
Resolution 0.1 volt
Accuracy 45-66 Hz 0.8 percent + 3
Input Impedance 360 kΩ
Overload Protection 660 volt RMS
Continuity Testing (RLO)
Range (Autoranging) 20/200/2000 Ω
Resolution 0.01/0.1/1 Ω
Open Circuit Voltage >4 volt
Insulation Resistance Measurement (RISO)
Test Voltages 50, 100, 250, 500, 1000 volt
The accuracy of Test Voltage (at rated test current) +10 percent, -0 percent
Test Voltage 50 volt
100 volt
250 volt
500 volt
1000 volt
Insulation resistance range 20/50 MΩ
20/100 MΩ
20/200 MΩ
20/200/500 MΩ
20/200/1000 MΩ
Resolution 0.01/0.1 MΩ
0.01/0.1 MΩ
0.01/0.1 MΩ
0.01/0.1/1 MΩ
0.01/0.1/1 MΩ
Test Current 1 mA at 50 kΩ
1 mA at 100 kΩ
1 mA at 250 kΩ
1 mA at 500 kΩ
1 mA at 1 MΩ
Loop and Line Impedance (ZI)
Range 10/0.001 Ω/High Current mΩ Mode
Resolution 0.01/0.1/1 Ω
Prospective earth fault current, PSC test
Range 1000 Amps/10 kA (50 kA)
Resolution 1 Amps/0.1 kA
Computation Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
RCD Testing, RCD Types Tested
RCD Type AC¹
G²,S³
Model 1663 A4, AC¹, G²,S³
Notes Responds to AC
General, no delay
Time delay
Responds to pulsed signal
Responds to smooth DC signal
Tripping speed test (ΔT)
Current settings¹ 10, 30, 100, 300, 500, 1000 mA – VAR
10-30-100 mA
Multiplier x ½, x 1
x 5
Measurement Range RCD Type G 310 ms
50 ms
RCD Type S 510 ms
160 ms
Notes 1000 mA Type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)
Current Range 30 percent to 110 percent of RCD Rated Current
Step Size 10 percent of IΔN²
Dwell Time Type G 300 ms/step
Type S 500 ms/step
Measurement Accuracy ±5%
Specified Trip Current Ranges (EN 61008-1) 50 to 100 percent for Type AC
35 to 140 percent for Type A (>10 mA)
35 to 200 percent for Type A (≤10 mA)
50 to 200 percent for Type B
Notes 30 to 150 percent for Type A IΔN > 10 mA
30 to 210 percent for Type A IΔN = 10 mA
20 to 210 percent for Type B
Earth Resistance Test (RE)
Range 200/2000 Ω
Resolution 0.1/1Ω
Frequency 128 Hz
Output Voltage 25 volt
Phase Sequence Indication
Icon  Phase Sequence Indicator is Active.
Size 100 x 250 x 125 mm
Weight 1.3 Kg
Includes:
  • 6 x AA Batteries
  • Zero Adapter
  • Heavy-Duty Mains Cord
  • STD Standard Test Lead Set
  • Padded Carrying and Waist Strap
  • Quick Reference Guide
  • TP165X Remote Control Probe and Lead
  • User Manual on CD-ROM
  • Hard Carry Case

Clear All

Your Recently Viewed Products

Oops! Something went wrong there and we were unable to load the page you requested.